Panelboards with Smart Metering


Description

An efficient addition to your Lighing Controls and Energy Management Systems. The Benjamin Smart Panel features circuit-level power metering
and remote controllable breakers to help you save energy.


Features

  • Power Metering on all branch circuits and mains with local data logging that provides easy identification of areas with high energy use.
  • Available with remote switchable branch breakers which can be controlled through scheduling, events, or local I/O.
  • Access metering data remotely using standard web browsers, no software install or license fees.
  • Industry Standard communication protocols are supported for integration with Building Management Systems.
  • Built to order, customized to your specifications, including retrofit upgrades to existing enclosures.

Specifications

Voltage Ratings 120/240V 1Ø 3W 208Y/120V 3Ø 4W 480Y/277V 3Ø 4W
AIC Ratings 65kAIC@240V Fully Rated to 100kAIC Series Rated
14kAIC@480Y/277V Fully Rated to 65kAIC Series Rated
Branch Circuit Breaker Options 1 Pole Ratings: 15A, 20A, 30A Controlled, 15A to 100A non-controlled
2 Pole Ratings: 15A, 20A, 30A Controlled, 15A to 100A non-controlled
3 Pole Ratings: 15A to 100A non-controlled
Mains Configurations Lugs Ratings: 100A, 225A, 400A, and 600A Rated
Breaker Ratings: 100A, 225A, 400A, and 600A Rated
Power Measurement Mains Current Accuracy 1% of reading from 1% to 100% of nominal rated current
Mains Voltage Accuracy 0.5% of reading from 90 to 600 VAC Line to Neutral
Mains Power Data Voltage, Current, Watts, PF, VA, VAR, HZ, WHrs, VAHrs, VARHrs
Branch Current Accuracy 1% of reading from 0.15 Amps to 100 Amps
Branch Circuit Data Current, Watts, PF, VA, VAR, WattHrs, VAHrs, VARHrs
Data Update Rate 1 second for all real-time values
Communications DMX-512, Modbus 485, Modbus TCP/IP, Bacnet IP, Web Server