Breaker Control Panel with DMX


Description

A panelboard offering remote on/off control of the branch circuits using standard DMX-512, DMX-RDM, or ACN connectivity.


Features

  • Remotely operate Eaton circuit breakers via DMX or ACN protocols.
  • Built-in delay for sequential breaker operation reduces in-rush current impacts from LED driver loads.
  • All circuit capacities utilize industry standard 20" width enclosure.
  • Configurations are built to order and arrive from our factory fully assembled and tested.
  • Metering available on Mains and Branch Circuits.
  • Industry Standard communication protocols are supported for integration with Building Management Systems or use the built in scheduler to control circuits.

Specifications

Voltage Ratings 120/240V 1Ø 3W 208Y/120V 3Ø 4W 480Y/277V 3Ø 4W
AIC Ratings 65kAIC@240V Fully Rated to 100kAIC Series Rated
14kAIC@480Y/277V Fully Rated to 65kAIC Series Rated
Branch Circuit Breaker Options 1 Pole Ratings: 15A, 20A, 30A Controlled, 15A to 100A non-controlled
2 Pole Ratings: 15A, 20A, 30A Controlled, 15A to 100A non-controlled
3 Pole Ratings: 15A to 100A non-controlled
Mains Configurations Lugs Ratings: 100A, 225A, 400A, and 600A Rated
Breaker Ratings: 100A, 225A, 400A, and 600A Rated
Power Measurement Mains Current Accuracy 1% of reading from 1% to 100% of nominal rated current
Mains Voltage Accuracy 0.5% of reading from 90 to 600 VAC Line to Neutral
Mains Power Data Voltage, Current, Watts, PF, VA, VAR, HZ, WHrs, VAHrs, VARHrs
Branch Current Accuracy 1% of reading from 0.15 Amps to 100 Amps
Branch Circuit Data Current, Watts, PF, VA, VAR, WattHrs, VAHrs, VARHrs
Data Update Rate 1 second for all real-time values
Communications DMX-512, DMX-RDM, ACN, Modbus 485, Modbus TCP/IP, BACnet/IP